PLC Omron CP1H

Omron CP1H PLC

CPU, USB Networking Computer Interface, 20 kB Program Capacity, 24 Inputs, 16 Outputs

 Pulse output for 4 axes. Advanced power for high-precision positioning control.

• High-speed counters. Differential phases for 4 axes. Easily handles multi-axis control with a single unit.

• Eight interrupt inputs are built in. Faster processing of approximately 500 instructions speeds up the entire system.

• Serial communications. Two ports. Select Option Boards for either RS-232C or RS-485 communications.

• Ethernet Communications. Enabled by using an Option Board. Two ports can be used as an Ethernet port to perform. Ethernet communications between the CP1H and a host computer.

• Built-in Analog I/O. XA CPU Units provide 4 input words and 2 output words.

• USB Peripheral Port. Another standard feature.

• The structured text (ST) language. Makes math operations even easier.

• Can be used for the CP1W series and CJ series Unit. The extendibility of it is preeminently good.

• LCD displays and settings. Enabled using Option Board.

General Specifications

 

TypeAC power supply modelsDC power supply models
ModelCP1H-[][][]-ACP1H-[][][]-D
Power supply 100 to 240 VAC 50/60 Hz 24 VDC
Operating voltage range 85 264 VAC 20.4 to 26.4 VDC
(with 4 or more Expansion Units and
Expansion I/O Units: 21.6 to 26.4 VDC)
Power consumption 100 VA max. (CP1H-[][][]-A) 50 W max. (CP1H-[][][]-D)
Inrush current * 100 to 120 VAC inputs:
20 A max. (for cold start at room
temperature)
8 ms max.
200 to 240 VAC inputs:
40 A max. (for cold start at room
temperature),
8 ms max.
30 A max. (for cold start at room
temperature)
20 ms max.
External power supply 300 mA at 24 VDC None
Insulation resistance 20 MΩ min. (at 500 VDC) between the
external AC terminals and GR terminals
No insulation between primary and secondary
for DC power supply
Dielectric strength 2,300 VAC at 50/60 Hz for 1 min between
the external AC and GR terminals, leakage
current: 5 mA max.
No insulation between primary and secondary
for DC power supply
Noise immunity Conforms to IEC 61000-4-4. 2 kV (power supply line)
Vibration resistance Conforms to JIS C60068-2-6. 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz,
acceleration: 9.8 m/s2 in X, Y, and Z directions for 80 minutes each. Sweep time:
8 minutes × 10 sweeps = total time of 80 minutes)
Shock resistance Conforms to JIS C60068-2-27. 147 m/s2 three times each in X, Y, and Z directions
Ambient operating
temperature
0 to 55°C
Ambient humidity 10% to 90% (with no condensation)
Ambient operating
environment
No corrosive gas
Ambient storage
temperature
-20 to 75°C (Excluding battery.)
Power holding time 10 ms min. 2 ms min.
Visitors: 90,276